C190 Series Alternators
for Use in Hazardous Locations
Installation Instructions
This symbol is used to indicate presence
of hazards that can cause severe personal
injury, death or substantial property damage.
WARNING
Installation Instructions
Explosion hazard. Do not open when an explosive
atmosphere is present. Improper installation of
alternator in an explosive environment can cause
severe personal injury, death, or substantial property
damage. Alternator must be installed by a qualified
person trained and familiar with requirements for
selection, installation, and maintenance of flame-
proof equipment to IEC 60079-14 and IEC 60079-17
respectively.
Person In Authority” is defined as the employee
of a company taking full responsibility for the safety,
welfare, and supervision of all other employees
under their control. (See Inspection and Mainte-
nance Section referenced above.)
WARNING
The alternator contains no user serviceable
parts. DO NOT DISMANTLE. Failure to observe
any instructions in the installation instruction may
invalidate any certificate or warranty agreement.
WARNING
1. Gland and cable and pulley/fan are specified and
ordered separately and are factory-installed. Cable
and gland have their own application requirements.
Cable entry temperature may be 40º C
above ambientcable to be suitable.
Contact C.E. Niehoff & Co. for:
Sira IECEx Certificate of Conformity IECEx SIR 09.0144X
SIRA ATEX Certificate of Conformity Sira 09ATEX1345X
Quality Assurance Certificate of Conformity Sira 0518
The alternator incorporates flameproof joints with dimensions that are
other than the relevant maximum or minimum, specified in Table 1 or
IEC 60079-1. The user shall contact the original manufacturer for infor-
mation on the dimensions of the flameproof joints.
The user shall refer to the manufacturer’s instructions with respect to the
enclosure providing a degree of ingress protection IP66.
DO NOT DISASSEMBLE. The cover O-ring may
dislodge and cause failure of the flameproof
protection features. Verify that there is NOT a
gap between the cover and the alternator hous-
ing. Torque the nine cover bolts (M6x1x25 6g
Class 12.9. DIN 912) to 13.5 Nm/120 lb.in., which
incorporate a steel zinc-plated washer (7.10x
12.00-12.12x 1.0mm thick) complete with bonded
seal provided with each bolt.
WARNING
WARNING
2 Mount alternator on a suitable bracket and secure
with hardware per alternator drawing on page 2 of
these instructions.
3. Ground bolt torque is 14.9 Nm/132 lb. in. Clean sur-
faces of all corosion and apply a suitable corrosion
inhibitor over ground connction for protection.
4. Secure output and ground cables within 12 inches
(300mm) of gland or terminal to prevent rotation
and loosening of cable at terminal.
5. Connect output cable from alternator to connections
as shown in diagram on page 4.
6. Perform a final inspection on the installation.
7. Install suitable alternator drive belt.
8. Start engine. Confirm the operation of charging
system meets specification.
TABLE 1—Conductor Sizes
Provision Internal Earthing Bonding conductor size = CSAMIN
1
*CSAMAX16mm
2
(5.5 Awg) CSAMINCSAMIN
2
16mm
2
<CSAMAX35mm
2
(2 Awg)
CSAMIN16mm
2
(5.5 Awg)
3
CSAMAX>35mm
2
(2 Awg) CSAMIN0.5 x CSAMAX
* Cross Sectional Area (CSA) of largest cable conductor = (CSAMAX)
Provision
External Earthing Bonding conductor size = CSAMIN
1
CSAMIN4.0mm
2
(11.5 Awg) CSAMIN=[8 Awg (8.4mm
2
)
INSTALLED]
Figure 1 – Alternator Nameplate Data
MODEL, VDC, ADC, ISOL GND
Repair of this equipment shall only be carried out by C.E. Niehoff & Co.
Page view 0
1 2 3 4

Summary of Contents

Page 1 - C190 Series Alternators

II154EPage 1 of 4C190 Series Alternators for Use in Hazardous LocationsInstallation Instructions This symbol is used to indicate presence

Page 2 - Page 2 of 4

II154EPage 2 of 4Figure 2 – Alternator Outline Drawing

Page 3 - Page 3 of 4

II154EPage 3 of 4ALTERNATOR CHARACTERISTICS FOR: C192/C193OUTPUT CURVE: OUTPUT AMPERES VERSUS ALTERNATOR SHAFT SPEED IN RPM AT 14.0 OR 28.0 VOLTS,RESP

Page 4 - Page 4 of 4

C. E. Niehoff & Co. • 2021 Lee Street • Evanston, IL 60202 Tech Services Hotline 800-