TG0055A
Table of Contents
Section A: Component Description .....................................2
Section B: Basic Troubleshooting .......................................2
Section C: Advanced Troubleshooting ................................3
Battery Conditions
Until temperatures of electrical
system components stabilize, these
conditions may be observed during
cold-start voltage tests.
Maintenance/Low Maintenance Battery
Immediately after engine starts, system volts are
lower than regulator setpoint, amps are medium.
35 minutes into charge cycle, system volts
increase, amps decrease.
510 minutes into charge cycle, system volts
increase to, or near, regulator setpoint and amps
decrease to a minimum.
Low maintenance battery has same characteristics
with slightly longer recharge times.
Maintenance-free Battery
Immediately after engine starts, system volts are
lower than regulator setpoint, low charging amps.
Once charge cycle begins, low volts and low amps
are still present.
After alternator energizes, voltage will increase
several tenths. Amps will increase gradually, then
quickly, to medium to high amps.
F i n a l l y, v o l t s w i l l i n c r e a s e t o s e t p o i n t a n d a m p s w i l l
decrease.
The time it takes to reach optimum voltage and amper-
age will vary with engine speed, load, and ambient tem-
perature.
High-cycle Maintenance-free Battery
These batteries respond better than standard mainte-
nance-free. Charge acceptance of these batteries may
display characteristics similar to maintenance batteries.
AGM (Absorbed Glass Mat) Maintenance-free Battery
These dry-cell batteries respond better than standard
maintenance-free. If battery state of charge drops to
75% or less, batteries should be recharged to 95% or
higher separately from the engine’s charging system to
avoid damaging charging system components and to
provide best overall performance. Charge acceptance of
these batteries may display
characteristics similar to
maintenance batteries.
NOTICE
Hazard De nitions
This term indicates special instructions
on installation, operation or mainte-
nance that are important but not
related to personal injury hazards.
NOTICE
Troubleshooting Guide
for N2013 Battery Isolator
Battery Charge Volt and Amp Values
Volt and amp levels fluctuate depending on the battery state
of charge. If batteries are in a state of dischargeas after
extended cranking time to start the enginesystem volts
will measure lower than the regulator setpoint after the
engine is restarted and system amps will measure higher.
This is a normal condition for the charging system; the
greater the battery discharge level, the lower the system
volts and the higher the system amps. The volt and amp
readings will change as batteries recover and become fully
charged: system volts will increase to regulator setpoint
and system amps will decrease to low level (depending on
other loads).
Low Amps: Minimum or lowest charging system amp
value required to maintain battery state of charge,
obtained when testing the charging system with a fully
charged battery and no other loads applied. This value
will vary with battery type.
Medium Amps: System amps value which can cause
the battery temperature to rise above adequate charg-
ing temperature within 4-8 hours of charge time. To
prevent battery damage, the charge amps should be
reduced when battery temperature rises. Check battery
manufacturer’s recommendations for proper charge
amp rates.
High Amps: System amps value which can cause
the battery temperature to rise above adequate charg-
ing temperature within 2-3 hours of charge time. To
prevent battery damage, the charge amps should be
reduced when battery temperature rises. Check battery
manufacturer’s recommendations for proper charge
amp rates.
Battery Voltage: Steady-state voltage value as mea-
sured with battery in open circuit with no battery load.
This value relates to battery state of charge.
Charge Voltage: Voltage value obtained when the
charging system is operating. This value will be
higher than battery voltage and must never exceed
the regulator voltage setpoint.
B+ Voltage: Voltage value obtained when measuring
voltage at battery positive terminal or alternator B+
terminal.
Surface Charge: Higher than normal battery voltage
occurring when the battery is disconnected from
battery charger. The surface charge must be removed
to determine true battery voltage and state of charge.
Significant Magnetism: Change in strength or
intensity of a magnetic field present in alternator
rotor shaft when the field coil is energized. The
magnetic field strength when the field coil is energized
should feel stronger than when the field is not ener-
gized.
Voltage Droop or Sag: Normal condition occurring
when the load demand on alternator is greater than
rated alternator output at given rotor shaft RPM.
Page view 0
1 2 3

Summary of Contents

Page 1 - Troubleshooting Guide

Page 1TG0055ATable of ContentsSection A: Component Description ...2 Section B: Basic Troubleshooting ...

Page 2

Page 2TG0055ASection A: Component Description and OperationN2013 Battery Isolator Description and OperationN2013 battery isolator used with this charg

Page 3

Page 3TG0055ASection C: Advanced TroubleshootingIf you have questions about your alternator or any of these test procedures, or if you need to locate